Reducing Power Factor Cost
Why improve yourpower factor?
Save money onutility bills
Increase internal electrical system capacity
Improve voltage drop at point of use
FACTSHEET Energy Efficiency
Real Power
Apparent Power
Low power factor is expensive and inefficient. Many utility companiescharge large commercial and industrial customers an
additional fee when power factor is less than about 0.95. Low powerfactor also reduces an electrical system’s distribution capacity
byincreasing current flow and causing voltage drops. This factsheet describes power factor and explains how you can improve your power
factor in order to reduce electric bills and enhance your electrical system’s capacity.
Why Improve Your Power Factor?
Some of the benefits of improving your power factor are:
Your utility bill will be smaller. Low power factor requires an increase in the electric utility’s transmission and distribution
capacity in order to handle the reactive power component caused by inductive loads. Utilities usually charge large customers with power
factors less than about 0.95 an additional fee. You can avoid this additional fee by increasing your power factor.
Your internal electrical system’s capacity will increase. Uncorrected power factor will cause increased losses in your electrical
distribution system and limit capacity for expansion.
Voltage drop at the point of use will be reduced (i.e. improved). Voltages below equipment rating will cause reduced efficiency,
increased current, and reduced starting torque in motors. Under-voltage reduces the load motors can carry without overheating or stalling.
Undervoltage also reduces output from lighting and resistance heating equipment.
What is Power Factor?
AC power is transmitted with the least losses if the current is undistorted and exactly synchronized with the voltage. Light bulbs
and resistance heaters draw current exactly synchronized and proportional to voltage, but most other loads tend to draw current with a time
lag (i.e. phase shift) or to distort it (i.e. introduce harmonics). It takes more current to deliver a fixed amount of power when the
current is phase shifted or distorted. The ratio of the actual power transmitted (“real power”) to the apparent power that could have been
transmitted if the same current were in phase and undistorted is known as the power factor. It is always less than or equal to
1.
Power Factor = Real Power
Apparent Power
Reducing Power Factor Cost Factsheet
2
Figure 2. 0.7 Power Factor at 200kW
Before the growth in electronic loads, such as computers and adjustable speed motor drives, distortion was only a minor problem.
Instruments and analysis techniques for evaluating power factor were devised only to consider the phase shift component of power factor.
Phase shift is measured in degrees, but it is equivalent to time (where 360 degrees equals the time required for one full AC cycle). Today
this component of power factor is called the displacement power factor (DPF) to distinguish it from the true power factor (TPF) that
accounts for distortion as well as phase shift. Utilities that impose low power factor penalties tend to meter and bill only on DPF.
Ignoring the effects of harmonic distortion leads to some fairly simple mathematical relationships illustrated by the power triangle in
Figure 1.
Figure 1. Power Triangle
If you measure current with an ammeter and voltage with a voltmeter, you can multiply them to get apparent power. The real power
equals the apparent power multiplied by the cosine of the phase angle difference between voltage and current. DPF is exactly equal to the
cosine of the phase angle difference. A third power term is reactive power. The physical meaning of reactive power can be better understood
by considering the example plot of voltage and current for a motor using 200 kW and 0.7
power factor (see Figure 2).
The power cycles at twice line frequency, averaging +200 kW over a full cycle. At each instant the voltage multiplied by the
current equals instantaneous power. Even when both current and voltage are negative, the power is positive because a minus times a minus is a
plus. However, phase lag causes voltage to sometimes be positive when current is negative and vice versa. In these instants, power is negative
and the motor is actually a generator feeding power back into the system. One can think of apparent power as the total power exchange between the
motor and power line, the real power as the net power flow to the motor, and the reactive power as the component of apparent power that is
exchanged back and forth between the line and the motor.
Cause of Low Power Factor
Low power factor is caused mainly by induction motors, but also by inductive loads (such as transformers and magnetic lighting
ballasts). Unlike resistive loads that create work entirely by consuming watts or kilowatts, inductive loads require some current to create
a magnetic field, and the magnetic field facilitates the desired work. The total or apparent power required by an inductive device is a
composite of the following:
Real power (measured in kilowatts, kW)
Reactive power associated with components that alternately store energy and release it back to the line during each AC cycle
(measured in kilovars, kVAR) Reactive power required by inductive loads increases the amount of apparent power (measured in kilovolt amps,
kVA) in your distribution system. The increase in reactive and apparent power is reflected by the increase of the angle between the two,
causing the power factor to decrease.
Reducing Power Factor Cost Factsheet
3
Figure 4. Effect of Power Factor Correction
Correcting Your Power Factor
Some strategies for correcting your power factor are:
Install capacitors in your AC circuit to decrease the magnitude of reactive power. Capacitors draw leading reactive power. That
means their current is 180 degrees out of phase with inductive loads, so they are storing energy when inductive loads are releasing it back
to the line and vice versa. As shown in Figure 3, reactive power (measured in kVARs) caused by inductance always acts at a 180-degree angle
to reactive power from capacitors.
Figure 3. Capacitive Reactance/Inductive Reactance
The presence of both inductive and capacitive reactance in the same circuit results in the continuous alternating transfer of
energy between the capacitor and the inductive load, thereby reducing the current flow from the line. In a sense, energy is caught and
reflected back by the capacitor instead of having to flow all the way back and forth from the power generator. In Figure 4 the power
triangle shows an initial 0.70 power factor for a 100 kW (real power) inductive load. The reactive power required by the load is 102 kVAR.
By installing a 69-kVAR capacitor, the apparent power necessary is reduced from 143 to 105 kVA, resulting in a 27 percent reduction in
current. Power factor is improved to 0.95.
Replace over-sized motors with NEMA Premium™ efficiency motors of the right horsepower. Any motor’s power factor is dramatically
worse when it is loaded significantly below the full nameplate horsepower rating.
Shut down idling motors. When totally unloaded, even uncoupled, a motor still draws over half its full-load reactive
power.
Avoid operation of equipment above its rated voltage. Over-voltage increases reactive power. Capacitor suppliers and engineering
firms can provide the assistance you may need to determine the optimum power factor correction and to correctly locate and install
capacitors in your electrical distribution system. Be mindful that if harmonic distortion is significant in your power system, DPF analysis
techniques will understate your true reactive power and overstate your true power factor. DPF analysis may accurately reflect the power
factor metered and billed by your utility, but it will understate your in-plant distribution system losses. Moreover harmonic distortion
can cause a variety of other system problems including harmful resonance currents in capacitors you have installed to control DPF. If you
suspect significant harmonic distortion, you must address harmonic problems in conjunction with displacement power factor.
|